Narration of Electrical Logic Control for
a Complex Turn-Key Wastewater Treatment System with Accompanying
P&ID Drawings
PID - M1
As the water flows through the flume into the grid separation
chambers, the flow rate is analyzed by the flow meter, and
the flume flow meter provides an analog signal back to the
PLC. High flow rates greater than 1200 gpm, will provide
an alarm. Solenoid valves SSV-M1-01 & 02 will be activated
by the flow meter. The solenoid valves provide hot water
to wash the screens when the flow rate flows less than 100
gpm the solenoid valves will be shut off. The grit separator
is operated by a local control panel including the mixer,
the transfer pump and the conveyor. "Digital-in"
signals are provided back to the PLC for status of operation
and overload conditions to the PLC. A level control of slop
oil tank LS-01 provides an alarm status signal to a PLC,
activated on high level only. Sludge pump P-2 driven by
solenoid valve SV-M1-01 is operated by a switch in the main
control panel. The pH monitor pHA, mounted in the flume,
senses pH providing an analog signal back to the PLC. There
will be an alarm set on the pH if it is too high or too
low to alert the operator of the off-spec condition.
PID - M2
The water flows out of the headworks into equalization tank
#3 through air activated valve, M2-09. The level of water
in equalization #3 is sensed through the pressure transmitter
PIM2-03 providing analog signal to the PLC. When the water
level rises in tank #3 to a predetermined height approximately
5’ above the overflow elevation (20 feet), air activated
valve M2-10 will open providing outlet of the water to the
dissolved air flotation unit. The rate of flow will be sensed
through FITM-2-01 providing an analog signal to the PLC
indicating the flow rate. An analog out signal from the
PLC will drive the FCV flow control valve FCV-M2-01. The
PLC will provide an analog signal to the flow control valve
to adjust the flow rate to a preset level of 300 gpm. If
the water rises above the 25’ height it will go to
step 2. At step 2, transfer from equalization tank 1 &
2 will close. If the water level rises above the 30’
mark, air activated valve MV-M2-04 or MV-M2-05 depending
on the status of the equalization tank 1 and 2 will open
to divert a portion of the water into equalization tank
1 or 2, and will also sound an alarm to alert the operator
who will then make a decision if he should increase the
flow of the water to the DAF or bypass the DAF (to be discussed
when we move to PIDM3 & 4).
The rate of flow from equalization tank 3 will be adjusted
in 3 set increments of four specific cases preset into the
PLC that regulates the flow control valve to a predetermined
flow rate. The flow rate can be adjusted and proportioned
to the level of the tank. Certain chemicals must be fed
proportionately to the rate of flow.
Pressure transmitter M2-03 on equalization tank 2, and
M2-01 on equalization tank 1 also supply analog signals
to the PLC. The graphic screen of the PLC will graphically
depict the level of water in each of these three tanks on
a real time basis. When there is no operator present at
the plant, the operator will turn off air activated valve
M2-09 and divert the water to equalization tank 1 or 2.
Their function can be automated on a 24 hour time cycle
at the customer's option. The other equalization tank will
be utilized for emergency storage during high flows (in
rain event). pH meters M2-01, 02, and 03, are in the recirculating
lines to each respective equalization tank providing an
analog signal to the PLC to indicate off-spec water. Should
the water reach an acidic state, an alarm will alert the
operator, who will manually activate the supply of sodium
hydroxide. The caustic is pumped by pump P-17 and PID-M3
and diverted to the proper equalization tank by an air activated
valve M2-11 on equalization tank 3 and M2-07 on equalization
tank 2 and M2-03 on equalization tank 1. One of these three
valves must be opened and be indicated as open before the
metering pump P17 will be activated. All three valves provide
digital signals on their respective position to the PLC.
Return pumps P-12 and P-13 on equalization tank 3 are manually
activated from the control panel to pump the wastewater
back to the headworks. Switches on these pumps are off/auto
with the auto position permitting the pump to be operated
only when level is present within the tank. If low level
is indicated the pumps will not be activated. Digital signals
are provided to the PLC for status, both operating and overload,
for P12 and P13.
Mix pumps P-11, P-4, and P-3 are operated by off auto switches.
When the level controls indicate low level in each equalization
tank the respective mixing pumps will not be allowed to
operate.
The return pumps P-12 and P-13 both have flow indicators
in the line provided. The digital signal to the control
panel must indicate flow, if not, an alarm will be given
to the operator to show that the respective pump is inoperable.
When the liquid level is present in equalization tank 1
and 2 the operator will manually transfer the liquid to
the treatment system in equalization tank 3. In the case
of equalization tank 1, transfer pumps are P-6 and P-10.
The operator manually operates air activated valve M2-01
on equalization tank 1 and then manually turns on transfer
pump P-6. If after a 30 second delay the flow indicator
in the line of P6 does not indicate moving liquid; P-6 will
be turned off and an alarm will sound to the operator. Transfer
pump P10 has the same type of service air activated valve
MV-M2-06 at the bottom of equalization tank 2, which controls
the delivery of water from equalization tank 2. Should tank
3 sense a high level, the transfer pumps will be turned
off. Bleed pumps P-5 and P-9 utilized to transfer from equalization
tank 1 and 2 through the air activated valve similar to
the transfer pumps, slowly transfer the collected liquid
into equalization tank 3. Flow indicators sense the flow.
Should there be a loss of flow, pumping action will cease.
The pumps will automatically turn off upon sensing low level
in equalization tanks 1 or 2. The bleed pumps and the transfer
pumps will sense low level in respective equalization tanks
1 or 2 depending upon which air activated valve M2-01 or
M2-06 is open. When an air activated valve is opened, digital
signals to the PLC will display the status, indicating if
the valve is opened or closed. The color graphic monitor
provides real time display of the status, opened or closed,
of all air activated valves. Pumps P-7 and P-8 have an off/auto
switch in the main control panel. The respective pumps will
be operated from level controls in the sumps. If a high
level is indicated in the sump an alarm will be given to
the operator.
PID-M3
When flow through the air activated valve is permitted and
indicated through the FIT (on M-2 drawing), the mixers in
the waste conditioning tank, MX-2 3 & 4 will be activated.
pH will be adjusted with sulfuric acid and caustic soda
by metering pumps P-15 and P-16. Analog signals provided
from the PLC progressively sense the pH and proportionately
adjust the rate of flow of the required reagent pH so over-shoot
does not occur. Pump P-14 supplying the ferric chloride
will be preset at four different steps proportionate to
the water flow as indicated from the FIT (drawing M-2).
Polyelectrolyte is supplied through PM-M3-01 Polymixer with
control by an analog signal from the PLC and will provide
the rate of flow of polyelectrolyte. DAF #1 and #2 will
be manually activated, the operator will select which DAF,
1 or 2 will be in operation by opening and closing the respective
hand valves B-10 (located at the inlet of each DAF). When
the operator initiates one DAF versus the second, he will
then manually turn on the air activated bottom sludge removal,
then from the central control panel activates a recycled
pump. The recycled pump is controlled by the FIT. When flow
is indicated from equalization tank 3, the respective DAF
will be automatically activated. When recycle pump is activated
the respective air compressor supplying the air will also
operate and the collected sludges will be automatically
drained from the bottom of the DAF. Flow indicators in the
air line supply for each DAF will indicate an alarm, if
no flow of air is indicated. Also, a flow indicator is in
the recycle line and should loss of flow be indicated, an
alarm will be given. Sludge from the top of the DAF flows
by gravity to the sludge collection tank. When the level
control in the sludge collection tank indicates a high level,
the transfer pump P-21 will automatically be activated.
The collected sludge will be pumped until the low level
is sensed.
PID-M4
Level of water in tank T-47 is continuously analyzed and
displayed on the color graphic monitor through PT-4-01.
Transfer pumps P-22 and P-23 operated from hand/off auto
switches within the central control panel will transfer
the liquid from the surge tank to the air stripper. When
the level of the tank T-47 indicates high level, the blower
will start on the air stripper. After a delay of 15 seconds,
FI-M4-02 will check the status of the blower, if air is
flowing (FI-M4-02) is provided to alert the operator and
will turn on transfer pumps P-22 or P-23 which will alternate.
If the flow is not indicated, an alarm condition will sound.
On sensing high high level in tank T-47 air activated valve
(MV-M4-11) will open, transferring water directly to transfer
tank T-48 bypassing the air stripper. Pressure differential
indicator across the air stripper will automatically monitor
the differential pressure giving an alarm if the air stripper
is contaminated. An organic analyzer placed in the effluent
from the air stripper line will automatically monitor the
presence of hydrocarbons and should high level be indicated
an alarm will be given.
Pressure indicator (PT-M4-02) on tank T-48 will continuously
monitor the liquid level, providing a signal to transfer
pumps T-24, T-25 and T-26. The three pumps will alternate
with the second and third automatically being turned on
as the liquid level increases in transfer tank T-48. Flow
indicator (F1-M4-01) in the air line to the VOC unit will
continuously monitor the status of the air movement and
should the air flow cease a visual and audio alarm will
be provided to alert the operator. Temperature indicator
in the air line continuously monitors the temperature and
opens or closes steam valves (SSD-M4-01) providing the required
steam. The air blower will be operated from the main control
panel with a hand switch.
Level controls in tank T-49, desorbate surge tank, will
provide the level controls to turn on pump P-89 transferring
desorbate to the decant tank. Level controls in decant tank
(T-49) will sense the level of the liquid on the water side
of the baffle and turn on pump P-27 to transfer the accumulated
water directly to the headworks. Periodically the operator
will manually turn on pump P-28 to transfer the accumulated
hydrocarbons to the oil storage tank.
PID-M5
Liquid coming from the transfer tank T-48 is directed into
tank T-1 or T-2 through respective air activated valve depending
on the liquid level in each tank. The level control indicators
on both tanks T-1 and T-2 continuously monitor the status
of the level providing alarms if high level is indicated
and open the corresponding air activated valve on the stand-by
tank.
The operator must manually tell the system through a switch
which treatment train A or B shall be operated. Activating
train A or train B opens air activated valve AV-M5-03 or
AV-M5-04. Upon opening these valves the entire system would
be put into a ready state to process liquid should either
pump P-29, P-30 or P-31 be activated from the level indicators
in the storage tank. When T-1 and T-2 are at low level and
the pumps deactivated, the entire train shuts down, the
sand filter turns off and after the system is off for a
period of 30 minutes, fresh water is flushed through the
sand filter for a predetermined period of time to flush
the carbonates from the sand. Treatment train B operates
the same as treatment train A. When train A or B is in operation,
the final pH adjustment mixer will be in operation and the
pH will be adjusted. When the system turns off the final
pH adjustment tank it will remain active for a period of
approximately 30 minutes to allow accumulated water to drain
through the treatment train. The pH in final pH adjustment
tank is adjusted by an analog signal. Water overflows from
the pH adjustment tank to the surge tank. The surge tank
has a pressure transmitter providing a real time graphic
display of the liquid level. The pumps on M-6, P-86 and
P-87 are activated by the liquid level in the surge tank.
These three pumps will alternate.
The sludge that accumulates in the sludge thickener will
be pumped to the filter press. A low hydraulic pressure
sensor within the filter press senses clamping pressure.
The filter press will not permit P-83 to pump unless adequate
clamping pressure is maintained. When the compacting pump
(P-83) starts, timers in the control panel activate three
solenoid valves providing a progressive pumping pressure.
The first stage is set at 20 psig, the second stage is set
at 40 psig, and the third full compaction pressure at approximately
90 psig. When the liquid flow through pump P-83 reduces
to a preset low flow the flow indicator of the pump M5-05
provides a press full signal to the PLC. The PLC upon sensing
low flow will sound an alarm to alert the operator that
the press is full.
PID-M-6
The operation of P-85, P-86 and P-87 was previously discussed
on PID 5. Two air activated valves AV-M-6-01 and AV-M6-02
determine where the pumps will transfer the liquid. If M6-01
is opened, the liquid will be pumped through the GAC absorbers
1 and 2. If M6-02 is opened the water will be directed to
the sewer without passing through the GAC absorbers.
Pump P-88 transfers accumulated water in a reuse storage
tank to back flush the GAC absorbers. The manual back flush
has an automatic interlock to pump P-88. Should low level
be indicated in the storage tank, the pump will no longer
transfer liquid. Flow indicators are located in the lines
to the GAC absorbers to indicate which absorber is in the
primary mode and which one is in the secondary mode. PID
indicators are installed across each gas absorber to indicate
the pressure differential required to drive the liquid through
the beds. When the preset high pressure level is attained
and is exhibited on the PLC, an alarm will sound to alert
the operator of the internal back pressure.
PID-M-7
Cyanide wastewater accumulates in cyanide equalization tank
T-25. The pressure transmitter provides real time indication
of the level in the tank, graphically displaying the level
on the color graphic monitor. Upon sensing a preset level,
transfer pump P-55 is activated transferring accumulated
waste to cyanide oxidation stage 1 and stage 2. When the
liquid is being transferred the mixer MX-19A and MX-19B
are activated and chemicals may be added as determined by
the pH and the ORP instrumentation. When liquid does not
flow through the cyanide oxidation tanks pH and ORP instruments
will monitor the condition but chemicals will not be added.
Treated cyanide waste accumulates in lift tank T-28 as sensed
by the three level controls M7-M-01, M-02 and M-03. Upon
sensing the level either P-56 or P-57 are automatically
activated to pump the treated water to the equalization
tanks in the metal treatment area, P-56 and P-57 will alternate.
Should high level be indicated an alarm will sound and the
secondary pump will be activated and transfer of liquid
from tank T-25 will cease.
PID-M-8
Water will be permitted to accumulate in tank T-30 acid
batch equalization and T-30B alkaline batch equalization.
Pressure transmitters on each tank will continuously monitor
the presence of the liquid and provide a real time graphic
display of the level to the color graphic monitor. When
high level is indicated on either of the tanks, P-62 or
P-63 will be activated to transfer accumulated liquid to
the batch treatment tanks. Water will continue to be transferred
into the batch tank until a high level is indicated in the
batch tank. The respective pump will be discontinued. The
system will be locked out from transfer until the waste
has been treated and transferred. pH and ORP instruments
provided for each tank will provide analog inputs to the
PLC. Automatic programs are set in the PLC to treat either
cyanide waste or chromate waste or neutralization waste.
A switch on the local control panel has a selection switch
so the operator can select the treatment process that he
desires. Example: If cyanide is to be treated pH will be
raised with sodium hydroxide, hypochlorite will be added
to a preset ORP reading held for one hour, pH will be dropped
to 8, additional hypochlorite will be added and then the
pH will be raised to preset level, polymer will be added,
the mixer will operate 10 minutes after the polymer is added,
then it will shut itself off. After 2 hours of settling
time, an alarm will sound to indicate to the operator that
it is time to drain the tank. Conversely the chromate treatment
cycle is also programmed into the treatment system. Sludge
will be transferred to the local sludge thickener and the
compacting 5 cubic foot filter press (through pump P-73).
Controls to the filter press for low hydraulic pressure,
"press full" and progressive pressure steps will
be identical to the filter press located in the metal treatment
area.
Tanks T-33 and T-34 both have water fill circuits. A level
control built into the tank provides a low level which sounds
an alarm to indicate to the operator it is time to fill
the tank. He presses a local push button switch which allows
water to fill into the tank until the high level is attained.
He then manually turns on the mixer and adds chemicals as
required to mix up the batch.
PID-M-9
Lime silo has an ultrasonic level control which provides
a signal to the PLC. The quantity of lime remaining in the
silo is graphically displayed on the screen.
The liquid lime slurry or "milk" is automatically
prepared. Upon sensing low level in the lime make-up slurry
tank, fresh water is added to raise to the high level. At
the same time the conveyor starts transferring lime into
the mix tank. The vane feeder on the bottom of the lime
silo is activated to deliver lime at preset rate. At the
completion of the preset time cycle, the vane feeder turns
off. The conveyor is allowed to run an additional 5 minutes
to purge itself of all lime. While the lime is being transferred
from the silo an air slide system at the bottom of the silo
is activated to shift the lime to the center outlet. Both
vane feeder and conveyor provide digital signals back to
the PLC indicating the status of either overload condition
or operation.
Pump P-94 air diaphragm transfer pump, will transfer lime
from the lime mixed tank to the lime slurry tank located
in the metals treatment area. Upon sensing low level in
the lime slurry tank, T-24 on PID-M10, pump P-94 is activated
to transfer liquid lime. Upon the completion of the transfer
by sensing the high level in the slurry tank, P-94 is stopped.
Fresh water is added for a period of 30 seconds to the input
side of the pump to flush the lime slurry from the pump
and through the line to tank T-24 prohibiting the build
up of lime in the lime transferred line.
Lime feed pump P-78 transfers lime to the sludge conditioning
tank T-37, which occurs when solids are being transferred
from either the DAF sludge tank or the sludge tank in the
headworks. Upon completion of the transfer of the required
lime, a fresh water flush valve opens flushing fresh water
to T-78 prohibiting the build up of lime within the pump
or the line.
Ferric chloride tank T-35 has a pressure transmitter on
the tank providing the level of ferric chloride. Upon sensing
a preset reorder level, an alarm will sound on the control
panel and the tank will flash until reorder has been accomplished.
Pump P-79 will pump ferric chloride to the sludge conditioning
tank. Transfer of the ferric chloride is done only when
solids are being transferred from the DAF or the headworks.
An additional air diaphragm pump is located on the ferric
chloride storage tank to transfer liquid ferric chloride
to tank T-23 on PID-M10. The ferric chloride tank operates
very similar to the lime. Upon sensing low level, ferric
chloride is automatically transferred from the bulk tank
to the day tank.
Add mix is supplied to the sludge conditioning tank by
pump P-80. This is a hand-off-auto function. The operator
must place it in the auto condition which will transfer
add mix whenever solids are being transferred from the DAF
to the headworks. The operator may also turn it on by hand
to add additional add-mix. Conditioned sludge in T-37 flows
by gravity into T-38 and then is pumped through P-81 and
P-82 into one of the two large sludge thickeners. Level
controls in T-38 indicate the level of the surge tank and
turn on P-81 and P-82 as required. Transfer of sludge from
the sludge thickeners to the filter press is a manual transfer.
The filter press is equipped with a low hydraulic pressure
similar to the two previous filter presses and a low pressure
progressive pump step control and as well as low flow to
indicate press full like the other two presses.
The filtrate exiting the filter press is transferred to
tank T-41 which has three level controls providing digital
inputs to the PLC to operate P-90 and P-91, to transfer
the water to the headworks. T-39 hot wash tank has level
controls to indicate the low level and solenoid valves automatically
fill the water level back up to the high level.
The sludge dryer provides digital input signals for the
status of the drive motor to the control PLC.
PID-M10
Low level signals are provided for T-17, T-18 and T-19.
High and low level signals are provided for T-20, T-21,
T-22, T-23 and T-24. T-24 lime slurry tank is automatically
filled as we discussed from PID-9. Tank T-23 the ferric
chloride day tank is also automatically filled as discussed
on M-9. T-20 and T-22 have automatic fill circuits for the
dilution water.
The lime slurry transfer pumps P-53 and P-54 have water
flush circuits.
When the pump turns off fresh water is flushed through
the pump and through the line to prohibit the accumulation
of the lime in the transfer line or pump.
PID-M-11
The treated water collects in the treated water storage
tank. When the tank is full the excess gravity flows to
the industrial sewer. Pumps with hydropneumatic pressure
reserves supply a continuous supply of pressurized water
to be reused as non-potable "Treated Effluent Storage"
(TES) or sent to the reverse osmosis unit (M-13) for further
purification.
PID-M-12
A boiler is installed to provide steam regenerate for the
gas phase carbon adsorption unit.
PID-M-13
A reverse osmosis unit is installed to remove the dissolved
salts from the (TES) producing reusable demineralized water.
The treated water initially flows through dual softeners
to remove the alkaline earth metals. The soft water is then
filtered and pumped through two array reverse osmosis membranes.
The permeate is stored in the RO tank (reverse osmosis)
and later reused as required. The reject, containing the
concentrated dissolved salts, is sent to the industrial
drain.